COMECA VERTICAL MOULDED BUS BAR – PATENTED SOLUTION AND UNIQUE DESIGN
by nhanvietjsc
GALAXIS SWITCHBOARD UP TO 6300A
GALAXIS switchboards combine maximum safety for personnel and equipment with reliability of your electrical installations and sustainability of your investments. Initially designed around a moulded bus bar used in nuclear power plants and O&G, this technology is recognized for the safety of installations provided. GALAXIS’s specific design ensures service continuity of your production and its future evolutions.
Our certifications provide compatibility with the major equipment brands. Equipment is also certified with the GemStartdigital thermal protection
VERTICAL MOULDED BUS BAR – PATENTED SOLUTION AND UNIQUE DESIGN
Unparalleled electrodynamic resistance and elimination of the risk of arc translation by maintaining the busbar over its entire length thanks to the molding resin. It also gives it success in the internal arc tests (IEC 61 641) required by petrochemical and nuclear industries (100KA / 1s – 220 KA Base peak). No mechanical maintenance required, this can often be the cause of defects and accidents due to improper tightening.
No risk of deformation of bars, they are blocked in the resin. No risk of dust accumulation (on supports) which in the long term would require maintenance in order to limit the risks of distances reducing necessary for a good level and respect of the dielectrics (often cause of priming).
Benefits
- Original Manufacturer providing also Tailor made solutions
- Multi-brand devices : SCHNEIDER ELECTRIC, ABB, SOCOMEC, SIEMENS
- Comfortable IEC61439 certification level at Hi rating of 100kA
- SHELL DEP (2008), type tested according to latest standards
- Risk free for operator, arc resistant with internal Arc Withstand of Class A as a minimum per construction
- Each part of GALAXIS refers to a drawing. Any part can be provided years after first delivery
- Main busbar has several positions (top / mid / rear)
- Cable access from front or rear
- Cable entry from top and / or Bottom
- Mid rear busbar tightenigs can be life warranteed with connections using TREP washers
- Vertical resin molded riser, guarantee of safety, without maintenance, without influence of the dust. Class I arc proof solution
- Hi riser rating with a rated current up to 2250A which allows high compacity of MCC panels
- Connection to vertical riser with auto-compensated intermediate stab connectors enclosed in a IP2x plastic housing
- WWW : Fully withdrawable equipments
- Replacement of drawers in live conditions
- Easy on site reconfiguration
- Height modularity of 25mm allows best size of each drawer
- REAR Access feeders are fully compatible with FRONT Access feeders (unlike most of the competition, if they have Rear Access)
- Better segregation of drawers, (horizontal partition sheet)
- Strong drawer with IP2x maintained in Test position
- Integrated cable connection : Native 4b form for cable connections with already embedded fixing bolts and screws. (Even in rear access, the operator can’t touch the connection under voltage due to 4b form with rubber protections)
- Form 4.7 available in option
Technical Characteristics
- Electrical data:
Features |
Value |
---|---|
Short-circuit current (max) | Up to 100 KA – 1s and 220KA peak |
Main bus bar rating | – Up to 6300A (top position)– Up to 4000A (rear position for limited height) |
Vertical bus bar | Up to 2200A |
IS333 | Withdrawable drawer up to 1000A AC1 |
Footprint optimisation | Half drawer up to 125A AC1 with moulded transposition block |
Rated impulse withstand voltage (Uimp) | 12 kV |
Rated insulation voltage (Ui) | 1000V |
Voltage rating (Ue) | Up to 690V AC |
Rated frequency (F) | 50/60Hz |
All earthing systems | TT, IT, TNC, TNS, TNC+TNS |
- Mechanical data:
Features |
Value |
---|---|
Service index | IS 333 evolution and modification without interrupting power. |
Connection type | WWWInterchangeable drawers on all GALAXIS range (rear or front access) |
Form | 3b/4b according to IEC 61439-2 and 4.7B according to BS standard |
Protection index | IP 31 to 42(For IP>42, please contact us) |
Access | Front or rear, top or bottom, for cables or bus ducts |
Dimensions(mini-maxi) | • Height : 2057 – 2400 mm• Width : 600 – 1000 mm
• Depth : 750 – 1000 mm |
Standards & Certifications
ISO 9001
IEC 61439-1 & 2
IEC 61 641 rev2 and rev3
Dep Shell 2008 for O&G applications
ATEX and H2S environments
ABS validations
Lloyds
Qualifoudre
Additional validations are made on major customer’s demand when switchboards are installed in sensitive sites.